Easy Riser Basic / ER-B

300 - 1,200 CFM

For concealed application virtually anywhere in the room, the Easy Riser Basic Vertical Stack (ER-B) comes standard in a heavy gauge 88" galvanized steel cabinet, insulated with 1/2" thick, neoprene coated fiberglass. This standard unit features a 1/2" OD copper tube coil, slide out blower assembly with quick disconnect plug, insulated drain pan and filter. Risers are ordered separately due to size changes throughout the building.
  • Heavy gauge galvanized steel cabinet with neoprene coated 1/2" thick fiberglass insulation with 3.35 PCF density.
  • Coils are made of 1/2" OD copper tube with aluminum fins (12 FPI) equipped with manual air vent. DX and steam coils do not include manual air vent. Coils are 100% underwater pressure tested at 350 PSI with a 300 PSI working pressure.
  • Galvanized drain pan is powder coated epoxy with a 1/8" thick elastomeric insulation and has a formed P-Trap drain connection.
  • Controls and motors are factory-wired and terminated in a junction box for single point power supply.
  • Three-speed, 115/1/60 PSC motor with quick connect plug.
  • 1/2" reinforced duct collar on return air opening.
  • Deluxe unit has single deflection supply air grille.
  • One inch fiberglass, throwaway filter.
  • Individually tagged, crated and shipped as scheduled for installation.
  • Protective cardboard covers grille openings during shipment and construction.
  • ETL approved, AHRI certified, 100% factory tested.
  • Soft-white, powder-coated epoxy cabinet that’s subjected to a 1,500 hour salt spray test in accordance with ASTM B117.
  • Drain Pans - stainless steel and double wall.
  • Insulation - fiberglass, foil face, elastomeric and double wall (solid or perforated) in 1/2” and 1" thicknesses.
  • Coils - copper fins/tubes, stainless steel fins/tubes, phenolic coated, stainless steel end plates. All options are available on one to six rows.
  • Three-speed, 208-230/1/50-60 or 277/1/60 PSC motor with quick-connect plug.
  • Systems - two or four pipe, hydronic cooling/heating, steam, direct expansion (DX) and/or electric heat.
  • Cabinet - enclosures; deluxe and concealed.
  • Controls - wide selection of factory mounted valves and controls.
  • Filters - two inch thick throwaway washable and metallic.
  • ECM™ motors; programmed 3 speed, or variable volume, 120-240/1 /60 or 277 /1 /60.
  • Grilles - supply and return, single and double deflection, additional openings and custom colors.
  • Outside air openings - motorized and manual outside air dampers.
  • Electric resistance heat from 1.0 to 7.5 kW.
  • Pedestal bases, Ultraviolet lights, grills with camlocks.
  • Risers and extensions available in type M, L and K copper with fiberglass, elastomeric and insulation.
  • Risers on Master fan coils have a 3" long and 5/8" swaged solder joint to connect to the slave unit.
  • Riser termination valve package.
  • Valve package controls - wide selection of factory-mounted valves and controls
  • Thermostat with quick connect plug.
  • Mixing Box
  • Manual
    • Motorized
    • Modulating
    • 3-Position Economizer
Full Louver Bar Style with Sound Shield
Partial Louver Bart Style with Sound Shield
Framed with Sound Shield
Louvered Pattern with Camlocks
Louver Bar Style with Camlocks
Solid Pattern with Camlocks

Customization

in any combination:

CONSTRUCTION

All unit chassis shall be fabricated of heavy gauge galvanized steel panels able to meet 1,500 hour salt spray test per ASTM B-117. All exterior panels shall be insulated with 1/2" thick, 1.5 pound per cubic foot, dual density fiberglass insulation rated for a maximum air velocity of 3600 f.p.m. Insulation shall conform to UL 181 for erosion and NFPA 90A and 90B for flame spread (25) and smoke developed (50) rating per ASTM E-84 and UL 723 and CAN./ULC, S102-M88.

All concealed units shall have a minimum 1" duct collar on the discharge.

All exposed units shall have exterior panels fabricated of cold rolled steel.


OPTION: Provide foil faced insulation in lieu of standard. Foil insulation shall meet or exceed the requirements stated above, and in addition, meet ASTM Standards C665 and C-1136 for biological growth in insulation. Insulation shall be lined with aluminum foil, fiberglass scrim reinforcement, and 30 pound kraft paper laminated together with a flame resistant adhesive. All exposed edges shall be sealed to prevent any fibers from reaching the air stream.

OPTION: Provide elastomeric Elastomeric foam insulation in lieu of standard. Insulation shall conform to UL 181 for erosion and NFPA 90A for fire,smoke and melting, and comply with a 25/50 Flame Spread and Smoke Developed Index per ASTM E-84 or UL 723. Additionally, insulation shall comply with Antimicrobial performance rating of zero, no observed growth, per ASTM G21. Polyethylene insulation is not acceptable.

DRAIN PANS

Primary condensate drain pans shall be single wall, heavy gauge, powder coated epoxy and extend under the entire cooling coil. Drain pans shall be of one piece construction and be positively sloped for condensate removal. Drain pans shall have primary and secondary drain connections.

The drain pan shall be externally insulated with a closed cell foam insulation. The insulation shall carry no more than a 25/50 Flame Spread and Smoke Developed Rating per ASTM E-84 and UL 723 and fungi resistant per ASTM G21/C1338, bacteria resistant per ASTM G22 and mold growth per UL 181.

OPTION: Provide a single wall primary drain pan constructed entirely of heavy gauge type 304 stainless steel for superior corrosion resistance. Stainless steel drain pans shall be externally insulated and meet or exceed the requirements stated above.

PIPING PACKAGES

Provide a factory assembled valve piping package to consist of a 2 or 3 way valve body, on/off motorized electric control valve actuator and two isolation ball valves. Control valves are piped normally closed to the coil. Maximum entering water temperature on the control valve is 180°F, and maximum close off pressure is 75 PSIG (1/2") or 44 PSIG (3/4"). Maximum allowed pressure shall be 300 PSIG.


OPTION: Provide 3 wire floating point modulating control valve in lieu of standard 2 position control valve with factory assembled valve piping package.

OPTION: Provide either a fixed or adjustable flow control device for each piping package.

OPTION: Provide pressure temperature ports for each piping package.

OPTION: Strainer for each package. Piping packages are shipped loose on all units and can be installed by request only.

FILTERS

All units shall be furnished with a two inch thick, 30/30 pleated filter, flatly mounted with spring loaded clips on the side access door for easy maintenance without the use of tools.

OPTION: Washable filters.

COILS

All cooling and heating coils shall optimize rows and fins per inch to meet the specified capacity. Coils shall have seamless copper tubes and shall be mechanically expanded to provide an efficient, permanent bond between the tube and fin. Fins shall have high efficiency aluminum surface optimized for heat transfer, air pressure drop and carryover.

All coils shall be hydrostatically tested at 350 PSIG air pressure under water, and rated for a maximum of 300 PSIG working pressure at 180°F maximum water temperature. Direct expansion cooling coils shall include a fixed orifice distributor and nozzle.

Steam coils shall be standard steam type suitable for temperatures above 35°F and 15 PSIG maximum working pressure.

OPTION: Coil casing shall be fabricated from 304 stainless steel.

OPTION: Provide a manual air vent fitting to allow for coil venting.

OPTION: Provide a manual water drain fitting for coil draining.

OPTION: Provide automatic air vents in lieu of manual air vents.

Cooling and heating coils shall be in the common coil casing, heating coils shall be furnished in the re-heat or preheat position on the unit with chilled water coils, and DX coil shall be in preheat position only.

ELECTRIC HEAT

Electric Duct Heaters shall be open coil type. Voltage, KW, size, number of steps and accessories shall be as shown. Units shall be U.L. listed for zero clearance and meet all applicable requirements of the latest National Electric Code and A.N.S.I. standards.

Element temperatures shall not exceed 400ºF below the melting point of the element alloy when energized with design voltage in still, free air at 75ºF ambient. The resistance element is the heart of the heater and should be designed with the operating temperature of the element alloy as the most important criterion. Because no air flow is likely to occur in at least some areas of the heater, this condition will be the basis for design for the entire element.

Frames shall be hot dipped galvanized after fabrication if spot welds are used. Spot welding must be coated after fabrication to prevent corrosion.

Mounting assemblies for the element support insulators shall pass between the insulators permitting free expansion of the insulators under high temperature conditions without cracking or breaking.

The total load of a heater should be divided into steps of no more than 30 amps for good design practice, or less if finer control is required. Units greater than 50 kW shall be controlled by a system with a recycling feature that will not allow all steps to be energized simultaneously.

The recycling feature prevents all steps from being energized simultaneously on power interruptions, cold start, thermostat manipulation, or other abnormal situations. All accessories are furnished as an integral part of each unit. Integrated accessories include air pressure switch, door interlock disconnect switch and transformer.

ELECTRICAL

Units shall be furnished with single point power connection. Installer shall provide an electrical junction box with terminal strip for motor and other electrical terminations. Electrical junction box can be ordered separately.

OPTION: Electrical junction box with multiple position ¼" spade terminal block to facilitate wiring terminations for the electric control valves
an thermostats.

OPTION: With Electric Heat, unit may be shipped loose or integrated.

OPTION: Include fusing, disconnects, sensors and switches.

Need Replacement Parts for Your Fan Coil Unit?

Fill out the form below

Similar Products

ER-B

More Info Vertical Stack
More...

For concealed application virtually anywhere in the room, the Easy Riser Basic Vertical Stack (ER-B) comes standard in a heavy gauge 88" galvanized steel cabinet, insulated with 1/2" thick, neoprene coated fiberglass. This standard unit features a 1/2" OD copper tube coil, slide out blower assembly with quick disconnect plug, insulated drain pan and filter. Risers are ordered separately due to size changes throughout the building.

ER-D

More Info Vertical Stack
More...

For exposed applications along walls and in corners, the Easy Riser Deluxe Vertical Stack (ER-D) is the model of choice. In addition to the same internal features as the ER-B, the Easy Riser Deluxe comes with an epoxy, powder-coat exterior and is subjected to a 1,500-hour salt spray test in accordance with ASTM B117. When greater architectural appeal is desired, the ER-B with cabinet enclosure is the preferred choice.

DR-B

More Info Vertical Stack
More...

The Designer Riser Basic Vertical Stack (DR-B) is for concealed applications along walls and in corners. This model comes standard in an extended 97" galvanized steel cabinet, insulated with 1/2" thick neoprene coated fiberglass. Like the ER-B, this unit features a 1/2" OD copper tube coil, slide out blower assembly with quick disconnect plug, insulated drain pan and filter.

DR-D

More Info Vertical Stack
More...

The Designer Riser Deluxe Vertical Stack (DR-D) is for exposed applications also along walls and in corners. In addition to the same internal features as the DRB, the Designer Riser Deluxe’s 97" cabinet includes a epoxy, powder coat exterior and is subjected to a 1,500 hour salt spray test in accordance with ASTM B117. When greater architectural appeal is desired, the DR-B with cabinet enclosure is the preferred choice.

ER-M / ER-S

More Info Vertical Stack
More...

The Easy Riser Master/Slave Vertical Stack units (ER-M and ER-S) have the same internal components as our Basic model, yet are designed to share a common riser set. The Master/Slave combination features two separate units piped to a common set of risers, each with individual valves and controls. These units come in an 88" galvanized steel cabinet.

DR-M / DR-S

More Info Vertical Stack
More...

The Designer Riser Master/Slave Vertical Stack units (DR-M and DR-S) have the same internal components as our Basic model, yet are designed to share a common riser set. The Master/Slave combination features two separate units piped to a common set of risers, each with individual valves and controls. These units come in a 97" galvanized steel cabinet.

TwinPack ER-D

More Info Vertical Stack
More...

The TwinPack is a master/slave combination that is pre-piped and housed in a common cabinet assembly at the factory. TwinPack Vertical Stack units include a UL 1 Hour Through Penetration Firestop W-L-7089 system. Local codes may dictate exact amount and placement of drywall. Each unit has it’s own set of valves and controls.

TwinPack DR-D

More Info Vertical Stack
More...

The TwinPack is a master/slave combination that is pre-piped and housed in a common cabinet assembly at the factory. TwinPack Vertical Stack units include a UL 1 Hour Through Penetration Firestop W-L-7089 system. Local codes may dictate exact amount and placement of drywall. Each unit has it’s own set of valves and controls.